• Non-Partial Discharge Power Supply
  • video

Non-Partial Discharge Power Supply

    It is used for AC withstand voltage and partial discharge test in fields such as transformers, circuit breakers, switches, GIS systems, cables, bushings, insulated terminals, etc.

    Product overview

    The W-F series partial discharge-free power supply utilizes an excitation transformer to activate either series or parallel resonant circuits. By adjusting the output frequency of the power supply, it induces resonance between the reactor's inductance and the specimen's capacitance within the circuit, generating a resonant voltage equivalent to the applied voltage on the specimen. Alternatively, the intermediate transformer can directly output the voltage to the primary side for induction withstand voltage testing. This system is applicable for AC withstand voltage testing and partial discharge testing of all electrical equipment.

    Product features:

    Output waveform is good, low voltage harmonic distortion rate, low harmonic content;

    Strong overload capacity, power unit modularization, can withstand the impact current of the motor, and does not cause voltage drop;

    Fast dynamic response, sudden load voltage transient change is small, fast recovery time;

    Intuitive display, easy to operate, using LCD Chinese and English touch operation display;

    Excellent stability, high frequency stability, produced by quartz oscillator, very stable and accurate frequency;

    Strong anti-interference, using optical fiber drive control, has strong anti-electromagnetic interference and reliability;

    High protection level, the surface of the equipment cabinet is treated with electrostatic spraying, and the PCB is treated with three-proof spray paint and potting compound.

     

    App industries

    It is used for AC withstand voltage and partial discharge test in fields such as transformers, circuit breakers, switches, GIS systems, cables, bushings, insulated terminals, etc.


     unit type

    WF60

    -31100

    WF60

    -31150

    WF60

    -31200

    WF60

    -31300

    WF60

    -31450

     power rating

    10KVA

    15KVA

    20kVA

    30KVA

    45KVA

    Input exchange indicators

    Power supply type

    Three phase four wire +PE

     voltage range

    380V(±15W)

     frequency range

    50/60Hz(±10W)

    Output AC characteristics

    Power supply type

    Single phase two wire

     voltage range

    0~800V- (standard)/0~1000V- (optional)

     current range

    12A

    18A

    25A

    37A

    60A

     frequency range

    Fixed frequency: 50/60Hz, frequency modulation: 30~300Hz

    Source effect

    0.1MFS

    Load effect

    0.1%F.S

     voltage accuracy

    0.1%F.S

    Frequency accuracy

    0.01%F,S

    Voltage harmonics

    2W

     response time

    5ms

    Volume increases

    20pC (standard)/10pC (optional)/5pC (optional)

     device efficiency

    90%

     overload capacity

    120%~150%,1min; 150W~200%,2s; 200%. Immediately shut off output

     system function

    Online adjustment function

    The output voltage and frequency can be adjusted online

    Quick Settings feature

    Multiple sets of output voltage and frequency can be customized

     memory function

    After power failure recovery, the last output mode and parameters can be remembered

     defencive function

    Input undervoltage and phase loss protection, output overvoltage, overcurrent, overload, short circuit protection, internal overheating protection, etc

    Display and communications

    Local operation

    LCD display screen

     display resolution

    Voltage: 0.1V, current: 0.1A, frequency: 0.1Hz, power: 0.1kW

    Display accuracy

    Voltage: 0.1MFS, current: 0.2%F.S, frequency: 0.01%, power: 0.3F.S

     telecommunication

    RS 485/LAN

     protocol

    Standard Modbus RTU/Modbus TCP/IP

    Safety performance

     compression strength

    2000Vdc/60s/ no breakdown

     insulation resistance

    20MΩ@500Vdc

     earthing resistance

    100mΩ

     noise

    65dB(A)

     service environment

     work environment

    The ambient temperature is-20~45, and the relative humidity is 0~95%, which can work continuously for 24 hours

     cooling-down method

    Fan forced air cooling

     levels of protection

    IP 21

     above sea level

    No more than 5000m@>2000m reduced use

    Power supply (W*D+H) mm

    400*560*800

    (including mobile wheels)

    400*660*800

    (including mobile wheels)

    500×8201100

    (including mobile wheels)

    500*820+1100

    (including mobile wheels)

    520*1160*1355

    (including mobile wheels)

     filter WD+Hmm

    600*400*162

    600*400*162

    600400*162

    600-400+162

    1000+572*162


    Get the latest price? We will reply as soon as possible (within 12 hours)