Product overview
The ZAC50 series is a high-precision, fast-response power supply with stable frequency and voltage regulation. It delivers pure and stable voltage waveforms even under complex grid conditions including unstable voltage/frequency, severe distortion, flicker, and voltage sags. This solution protects high-precision equipment from grid disturbances while overcoming the frequency-stabilization limitations of conventional parameter regulators, making it an ideal replacement for traditional voltage stabilizers.
● Wide input voltage range: can adapt to the rated voltage range of ±18%~±25%;
● High overload capacity: power unit is modular, can withstand more than twice the rated current without voltage drop;
● Fast dynamic response: sudden load voltage transient change <1%, recovery time <20ms;
· Good man-machine interaction: 7-inch touch operation display with resolution of 800*480;
● Strong anti-interference: optical fiber drive control, with strong anti-electromagnetic interference and reliability;
● High protection level: the surface of the equipment cabinet is treated with electrostatic spraying, and the PCB is treated with anti-corrosion paint and resin injection.
App industries
It is used in communication, instrumentation, medical equipment, household appliances power supply, precision instrument production and other fields.
unit type | ZAC50 -11100 | ZAC50 -31300 | ZAC50 -33450 | ZAC50 -331000 | ZAC50 -332000 | ZAC50 -334000 | ZAC50 -338000 |
power rating | 10KVA | 30KVA | 45KVA | 100KVA | 200KVA | 400KVA | 800KVA |
Input exchange indicators | |||||||
Power supply type | Single phase two wire +PE | Three phase four wire +PE | Three phase four wire +PE | ||||
voltage range | 176~264V:- | ||||||
frequency range | 30~100Hz | ||||||
Output AC characteristics |
| ||||||
Power supply type | Single phase two wire | Single phase two wire | Three phase four wire | ||||
voltage range | 220V- | ||||||
current range | 45A | 136A | 68A | 151A | 303A | 606A | 1215A |
frequency range | Fixed frequency: 50/60Hz | ||||||
Source effect | ≤0.1%F.S | ||||||
Load effect | ≤0.1%6F.S | ||||||
voltage accuracy | ≤0.1%F,S | ||||||
Frequency accuracy | ≤0.01%FS | ||||||
Voltage harmonics | ≤2W | ||||||
response time | ≤5ms | ||||||
device efficiency | ≥90% | ||||||
overload capacity | 120W~150%,1min; 150%~200%,2s; ≥200%, immediately shut off output | ||||||
system function |
| ||||||
Online adjustment function | The output voltage and frequency can be adjusted online | ||||||
memory function | After power failure recovery, the last output mode and parameters can be remembered | ||||||
defencive function | Input undervoltage and phase loss protection, output overvoltage, overcurrent, overload, short circuit protection, internal overheating protection, etc | ||||||
Display and communications |
| ||||||
Local operation | LCD display screen | ||||||
display resolution | Voltage: 0.1V, current: 0.1A, frequency: 0.1Hz, power: 0.1kW | ||||||
Display accuracy | Voltage: 0.1%F.S, current: 0.2%F.S, frequency: 0.01%, power: 0.3MF, S | ||||||
telecommunication | RS 485/LAN | ||||||
protocol | Standard Modbus RTU/Modbus TCP/IP | ||||||
Safety performance | |||||||
compression strength | 2000Vdc/60s/ no breakdown | ||||||
insulation resistance | ≥20MΩ@500Vdc | ||||||
earthing resistance | ≤100mΩ | ||||||
noise | ≤65dB(A) | ||||||
service environment | |||||||
work environment | The ambient temperature is-20℃~45℃, and the relative humidity is 0~95M. It can work continuously for 24 hours | ||||||
cooling-down method | Fan forced air cooling | ||||||
levels of protection | IP 21 | ||||||
above sea level | No more than 5000m@>2000m reduced use | ||||||
Size (W+D+H) mm | 400-660-800 (including mobile wheels) | 500*820+1105 (including mobile wheels) | 520*1160*1355 (including mobile wheels) | 650*1420*1470 (including mobile wheels) | 1550*850*1985 (including mobile wheels) | 1910*1160*1940 | 3100+90D+2080 |